Cashco P2 Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 8
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
IOM-P2
2
SECTION IV
IV. STARTUP
SECTION V
V. SHUTDOWN
SECTION III
III. PRINCIPLE OF OPERATION
1. Movement occurs as pressure variations register
on the diaphragm (7.1). The registering pressure
is the outlet, P
2
, or downstream pressure. The
range spring (15) opposes diaphragm move-
ment. As outlet pressure drops, the range spring
push es the diaphragm down, opening the port; as
outlet pres sure in creas es, the diaphragm push es
up and the port opening clos es.
2. A complete diaphragm failure will cause the reg u-
la tor to fail open.
The maximum outlet pressure is stamped on the body
as the upper range spring pres sure level, and is the
rec om mend ed “upper operative limit” for the sens ing
diaphragm (see Sec tion IV. Startup, Step 7). Higher
press ures could dam age the di a phragm. (Field hydro-
static tests fre quent ly de stroy di a phragms. DO NOT
HYDRO STATIC TEST THRU AN IN STALLED UNIT; ISO-
LATE FROM TEST.)
1. Start with the block valves closed. A by pass
valve may be used to maintain out let pres sure
in the down stream sys tem without changing the
fol low ing steps.
2. Relax the range spring (15) by turning knob (4)
counter clockwise (CCW) until ro ta tion comes to
a complete stop.
3. If it is a “hot” piping system, and equipped with
a bypass valve, slowly open the bypass valve
to preheat the system piping and to allow slow
ex pan sion of the piping. Closely monitor outlet
(down stream) pres sure via gauge to ensure not
over-pressurizing. NOTE: If no bypass valve is
in stalled, extra caution should be used in starting
up a cold system; i.e. do everything slowly.
4. Crack open the outlet (downstream) block
valve.
5. Slowly open the inlet (upstream) block valve ob-
serv ing the outlet (downstream) pressure gauge.
De ter mine if the regulator is owing. If not, slowly
rotate knob (4) clock wise (CW) until ow begins.
6. Continue to slowly open the inlet (upstream) block
valve until fully open.
7. Continue to slowly open the outlet (downstream)
block valve, especially when the downstream pip-
ing system isn't pressurized. If the outlet (down-
stream) pressure exceeds the desired pres sure,
close the block valve and go to Step 2, then return
to Step 4.
8. When ow is established steady enough that the
outlet (downstream) block valve is fully open, be-
gin to slowly close the bypass valve if installed.
9. Develop system ow to a level near its expected
normal rate, and reset the regulator set point by
turning knob (4) CW to increase outlet pressure,
or CCW to reduce outlet pressure.
10. Reduce system ow to a minimum level and ob-
serve set point. Outlet pressure will rise from the
set point of Step 9. The maximum rise in outlet
pressure on decreasing ow should not exceed
the stated up per limit of the range spring by greater
than 10%. Example: with 2-100 psig (.14-6.9 Barg)
range spring at low ow the outlet pressure should
not exceed 110 psig (7.6 Barg), if it does, con sult
factory.
1. On systems with a bypass valve, and where sys-
tem pressure is to be main tained as the reg u la tor
is shut down, slowly open the bypass valve while
closing the inlet (up stream) block valve. Fully
close the inlet (up stream) block valve. (When on
bypass, the sys tem pres sure must be con stant ly
observed and man u al ly reg u
lat ed. Close the
outlet (down stream) block valve.
2. If the regulator and system are to both be shut
down, slowly close the inlet (upstream) block
valve. Close the outlet (downstream) valve only
if reg u la tor re mov al is required.
CAUTION
Do not walk away and leave a bypassed
regulator unattended.
CAUTION
Vue de la page 1
1 2 3 4 5 6 7 8

Commentaires sur ces manuels

Pas de commentaire